產(chǎn)品分類(lèi)

Product category

產(chǎn)品展示 / products 網(wǎng)站首頁(yè) > 產(chǎn)品展示 > 高壓試驗(yàn)儀器儀表 > 微機(jī)繼電保護(hù)測(cè)試儀 > JYM-303三相多功能標(biāo)準(zhǔn)表(英文版)
JYM-303三相多功能標(biāo)準(zhǔn)表(英文版)

JYM-303三相多功能標(biāo)準(zhǔn)表(英文版)

簡(jiǎn)要描述:JYM-303 meter, developed by our company, is a standard electric energy meter with characteristics of wide-range, multifunction and high-precision. It has accuracy grade of 0.02. By adopting techniques

產(chǎn)品型號(hào):

所屬分類(lèi):微機(jī)繼電保護(hù)測(cè)試儀

更新時(shí)間:2016-02-18

廠商性質(zhì):生產(chǎn)廠家

詳情介紹

JYM-303三相多功能標(biāo)準(zhǔn)表(英文版)的詳細(xì)介紹

 

本產(chǎn)品由上海徐吉電氣有限公司精心推薦:

 

產(chǎn)品特性:

1. With cases of luxury sectional bar, A-series has a luxurious appearance. While with aluminum cases, B-series is portable, more smaller (it is the smallest one in domestic products of this kind. 355*145*185mm) , more lighter and easier to take.
2. Wide-range measuring:
Voltage measuring range (phase voltage):1~560V
   Current measuring range:                        10mA~120A
3. Measurement of various ways: It has ability to measure AC voltage , current , power (active power, reactive power, apparent power) and electric energy in four-quadrant with connection modes such as single-phase and four-wire three-phase Y/ three-wire Δ. In addition, it can measure reactive power and electric energy with ways of true reactive, cross-phase reactive power, artificial neutral point of reactive.
4. Multifunctional measurement:
a. Fundamental function of measuring for voltage, current, phase, frequency, active power, reactive power, power factor and error.
b. Measuring degree of stability of voltage, current and power.
c.Measuring degree of asymmetry of voltage and current amplitude in three-phase circuits.
d.Measuring degree of unbalancedness of voltage and current in three-phase circuits.
e.Measuring degree of asymmetry of the phase.
f.Display of vector diagram. There are a variety of display ways for vector diagram to meet the different display habits (such as clockwise rotation, counterclockwise rotation; the choice of the benchmark location between 12:00 o’clock and 3:00 o’clock; reference benchmark can be changeable; phase settings for display ways: 0~360°or ±180°).
g.Waveform display, harmonic analysis, distortion calculation. Display of frequency spectrum, it can display the amplitude, contents and phase of the harmonic. Frequency spectrum can be enlarged.
h.Dem measurement.
i.Measurement of space magnetic induction intensity.
j.Measurements of voltage drop of the device’s dotted terminal.
k.Measurement of the constant and frequency of the meter to be adjusted.
l.Measurement of power of fundamental wave.
m. It can adjust errors of three different kinds of meters (active power, reactive power, apparent power, voltage, and current).
n.There are three ports for pulses to output. And its constants can be set automatically or manually. Types of constants can be set also: active power, reactive power, apparent power, voltage, and current.
o. It can check the comprehensive error of device composed of three single-phase meters.
p. It can be used as three single-phase standard meters.
5. Measurement of power for fundamental wave: not only could it measure the full power (including powers of fundamental wave and orders harmonics), but also the fundamental power only.
6. Adjustment of electric energy error: it can adjust the estimate value of standard deviation and computation error of electric energy meters as well as calibration device for energy meter. Moreover, counts of pulse and constants of meters to be checked can be set automatically so as to work effectively. Especially for the multi-constant standard meter and the energy meter calibration device, it will be more convenient. By adopting the use of special compensation techniques, error-beating would not be large because of the small load (the low frequency of the energy pulses). It can display the current error, the value of the standard deviation estimate and the average error.
7.  Harmonic analysis: it can analyze the harmonics of voltage and current under 51 orders.
8. Display of data and graphics: it can display the measuring working condition and multiple measuring data directly. It can also display the waveform of the voltage and current to be measured, the phase vector graph of the voltage and current and waveform of harmonic analysis directly.
9. The measuring range can be switched manually or automatically.
10. With storage function, it can store 30 groups of data records which can be searched and browsed according to the condition.
11. With the function of Pinyin input method: Chinese Character, alphabet and symbol can be inputted.
12. Connection: the input port of the wide-range current is a public port, and there is no need to change connection mode while the current is changed, so it is very convenient to use.
13. Multi-use: it can be used as a standard-meter, also as a calibration device for energy meter. It can be used alone, with PC by remote communication, also with calibration device.
14. Multiple ports for communication: RS485, RS232, USB, and baud rate can be set when using asynchronous communication.
15. With 6.4(or 5.7)-inch 640*480 pixel TFT display, it shows clearly and colorfully.
16. Operation: human orient design, reasonable combination of the function and simple operating.

 

產(chǎn)品參數(shù):

1. Current measurement (Actual valid value RMS)
Range:0.2A、1A、5A、20A、100A, range switch automatically
Display range:0.00000mA~120.000A
Measurement error:distorted wave:±0.02%RD(10mA~120A)
 Fundamental:±0.02%RD(10mA~120A)
 2~21 harmonic:±0.1%RD(10mA~120A)
Measurement time base:1s~99s
2.  Voltage measurement (Actual valid value RMS)
Range:60V、120V、240V、480V  range switch automatically
Display range:0.00000V~576.000V
Measurement error:
distorted wave:±0.02%RD(40V~576V)
 Fundamental:±0.02%RD(40V~576V)
2~21 harmonic:±0.1%RD(40V~576V)
Measurement time base:1s~99s
3.  Power measurement
Measurement error:
Distorted wave active power:±0.02% RD(40V~576V,10mA~120A,PF≥0.5)
Sine wave reactive power:±0.02% RD(40V~576V,10mA~120A,PF≥0.5)
Sine wave apparent power:±0.02% RD(40V~576V,10mA~120A,PF≥0.5)
Fundamental active power:±0.02%(40V~576V,10mA~120A,PF≥0.5)
2-21 harmonic active power:±0.02%(40V~576V,10mA~120A,PF≥0.5)
Display range:6 digital display
4. Phase measurement(phase difference between each phase voltage and current)
Measurement error:±0.01°(40V~576V,10mA~120A)
Display range:0.000°~359.999°
5.Power factor measurement(each phase power factor and three phase power factor)
Measurement error:±0.0002(40V~576V,10mA~120A)
Display error:-1.00000 ~ 0 ~ +1.00000
6.Frequency measurement
Measurement range:45~70Hz;
Measurement error :±0.005%RD
Display error:44.9999Hz ~ 69.9990Hz
7.Harmonic content measurement
Harmonic times:2…51 ( fundamental wave as 50Hz)
Harmonic measurement error :±10%RD±0.1%(Rd as harmonic content reading)
Distortion Measurement error :±10%RD±0.1%(Rd as distortion reading)
8. Energy measurement
Measurement error:
Distorted wave active energy:±0.02%(40V~576V,10mA~120A,PF≥0.5)
Sine reactive energy:±0.02%(40V~576V,10mA~120A,PF≥0.5)
Sine active energy:±0.02%(40V~576V,10mA~120A,PF≥0.5)
Fundamental wave active energy:±0.02%(40V~576V,10mA~120A,PF≥0.5)
2-21 harmonic active energy:±0.1%(40V~576V,10mA~120A,PF≥0.5)
Display error:(0.00…999999)Wh、varh、VAh
9. Energy error measurement
Tested meter constant range:1~999999999999imp/kWh(kvarh、kVAh)
Pulse no. set range:1~9999999
10. Tested energy pulse input
Pulse electric level:5…12V
 input Frequency:2MHz (max)
Min. pulse width:250ns
Min. pulse interval:250ns
11. Standard energy pulse output
Pulse electric level:5V±5%,100mA
Output frequency:Rated frequency60kHz (while voltage、current limit, power factor as 1)
Max. frequency: 72kHz(While voltage limit、1.2 current limit,power factor as 1)
12.Standard deviation evaluated value
Voltage, current , active/reactive power, active/reactive energy                       standard deviation evaluated value≤0.002%
13.Variation caused by influence quantity
Measurement circuit voltage influence:≤0.004%(Power supply variation ±10%)
Measurement circuit frequency influence:≤0.004%(Power supply variation ±10%)
Auxiliary power supply voltage influence:≤0.002%(Power supply variation ±10%)
Auxiliary power supply frequency influence:≤0.002%(Power supply variation±5%)
Auxiliary power supply phase influence:≤0.002%
Reverse phase influence:≤0.002%
Current 3 times harmonic influence:≤0.004%
AC external magnificent influence(1m,400 turns):≤0.01%
14. Temperature
Temperature coefficient:≤0.0005% /℃
Self-heat influence:≤0.01%
Pre-heat time:≤30min
15.24h deviation:≤0.004%
16. Insulation resistance:
The insulation between voltage、current  input terminal and meter cover、power supply terminal and meter cover should not less than 100MΩ
Industrial frequency withstand voltage:
Between voltage、current input  terminal & power supply terminal and meter cover should withstand 50Hz sine wave 2kV  1min test;Between voltage circuit and current circuit; difference phase of current circuit should withstand 600V test.
17. Ambient
Rated temperature:23℃±2℃
Work temperature range:10℃~30℃
Max. work temperature range:0℃~40℃
Storage and transportation max. temperature range:-20℃~55℃
Relative humidity:≤85%
18. Others
Auxiliary power supply: 220V±15%,50Hz±10%
Power consumption: ≤30VA 
Cabinet: 355 × 185 × 145 mm。
                        i.              Weigh: 7.5kg



留言詢(xún)價(jià)

留言框

  • 產(chǎn)品:

  • 您的單位:

  • 您的姓名:

  • 聯(lián)系電話:

  • 常用郵箱:

  • 省份:

  • 詳細(xì)地址:

  • 補(bǔ)充說(shuō)明:

  • 驗(yàn)證碼:

    請(qǐng)輸入計(jì)算結(jié)果(填寫(xiě)阿拉伯?dāng)?shù)字),如:三加四=7

聯(lián)


主站蜘蛛池模板: 色欲色香天天天综合VVV| 六月婷婷缴清综合在线| 亚洲AV日韩综合一区| 色综合久久精品亚洲国产| 国产精彩对白综合视频| 区三区激情福利综合中文字幕在线一区亚洲视频1 | 亚洲成综合人影院在院播放| 久久婷婷五月综合97色一本一本| 色综合67194| 亚洲AⅤ优女AV综合久久久| 一本一道久久精品综合| 一本久久综合亚洲鲁鲁五月天| 国产精品亚洲综合| 亚洲婷婷综合色高清在线| 精品亚洲综合在线第一区| 狠狠色综合7777久夜色撩人| 久久精品综合电影| 国产亚洲综合视频| 亚洲综合成人婷婷五月网址| 亚洲av综合色区| 成人综合伊人五月婷久久| 色天使亚洲综合一区二区| 亚洲日本国产综合高清| 亚洲国产美国国产综合一区二区| 亚洲欧美日韩综合俺去了| 久久天堂AV综合合色蜜桃网| 久久综合色天天久久综合图片| 色综合伊人色综合网站| 成人综合激情另类小说| 亚洲综合一区二区三区四区五区| 五月丁香综合激情六月久久| 综合人妻久久一区二区精品| 中文字幕乱码人妻综合二区三区| 欧洲亚洲综合一区二区三区| 狠狠色丁香婷婷久久综合蜜芽 | 久久精品桃花综合| 久久久综合香蕉尹人综合网| 狠狠色噜噜狠狠狠狠色综合久AV| 色悠久久久久综合网香蕉| 精品综合久久久久久99| 色噜噜狠狠色综合中文字幕|